If you suspect there is a problem with the defrost control board, thermostat, or defrost timing here are the procedure for testing. This assumes that the system is properly charged.
Checking the Defrost Control Board
Checking the Defrost Thermostat The defrost thermostat is what determines when a defrost is needed and when the system should go out of defrost. Most defrost thermostats close at 28F +- 5F.
Final Notes
If you still are having a defrost problem, check the all wiring and connections for corrosion, opens, or shorts.
Want to learn more about heat pumps and air conditioning? Sign up for our HVAC Certification Course.
by Ron Walker
Checking the Defrost Control Board
- Turn off all power to the outdoor unit.
- On the control board, locate the two terminals where the defrost thermostat is connected.
- Disconnect the defrost thermostat.
- And connect a jumper across the defrost thermostat terminals on the control board. (Make sure the jumpers are connected properly, touching only the defrost thermostat terminals).
- The jumper simulates a cold coil and a defrost condition.
- At this time, locate the two test terminals on the defrost control board. Depending on the manufacturer it may say "Test", "Speed Up", or on a Trane system "Test" and "Test.Common". Double check!
- Place another jumper between the two test terminals.
- This will speed up the defrost timing cycle. 90 minutes = 21 seconds, 60 minutes = 14 seconds, and 30 minutes = 7 seconds.
- Turn the electrical power back on.
- Place the thermostat into heating.
- The unit should cycle in and out of defrost with the accelerated time limits as listed above.
- It is not recommended to leave the unit in the test mode for a prolonged period of time.
Checking the Defrost Thermostat The defrost thermostat is what determines when a defrost is needed and when the system should go out of defrost. Most defrost thermostats close at 28F +- 5F.
- Turn of the power to the unit.
- Disconnect and remove the sensor from the unit.
- Fill a small glass or container with ice and just enough water to cover the ice.
- Place a thermometer in the water and add salt until the temperature reads 20-25 degrees (I know... Who carries salt with them?).
- Fill another small container with water that is in the 70-75 degree range.
- Connect your ohmmeter between the two sensor leads.
- Place the the defrost sensor in the cold water solution.
- In about 60-90 seconds, the sensor should close and read continuity.
- Place the sensor in the warm water container.
- After another 60-90 seconds, the sensor should open and read infinite.
Final Notes
If you still are having a defrost problem, check the all wiring and connections for corrosion, opens, or shorts.